FixtureUnitFixture units in, pipe size out — the table the code actually uses.

Drain & Waste Sizing

DFU to drain size, and the slope every horizontal run needs.

5 articles

What size building drain for a house with 4 half bathrooms?

4 half bathrooms — building drain
3″
25 drainage fixture units at a ¼″ per foot fall — a 3″ drain carries 42
4 half bathrooms — building drain25 DFUTotal drainage fi…42 DFUCapacity of a 3″ …
Building drainat ¼″ per foot of fall3″
Total drainage fixture units4 × 4 for the bathrooms + 9 for kitchen and laundry25DFU
Capacity of a 3″ drain17 DFU of headroom left42DFU
Branch serving one bathroom4 DFU — toilet and basin only — no bath or shower2″
Water supply fixture units17WSFU
Supply mainHunter curve at 46–60 psi street pressure¾″

Notes

  • Fixture units are not fixtures. A DFU is a unit of probable simultaneous flow, not a count of drains. Six fixtures do not all discharge at once, and the tables are built on that probability — which is why 4 half bathrooms plus a kitchen and laundry comes to 25 DFU rather than a simple headcount.
  • Slope changes the answer more than most people expect. The same 3″ pipe carries — DFU at ⅛″ per foot and 50 at ½″. Too little fall and solids strand; too much and the water outruns them, which strands solids for the opposite reason. ¼″ per foot is the usual target.
  • A 3″ drain is capped by more than DFU. Most codes also limit how many water closets a 3″ line may serve regardless of the arithmetic, and at ⅛″ fall a 3″ building drain is not permitted at all. Check the water-closet limit as well as the number above.
  • The supply side answers a different question. 17 WSFU calls for a ¾″ main at typical street pressure — but length of run, elevation gain and meter size all pull that around, and a long run to an upstairs bathroom is the case where the table alone gets it wrong.
  • Figures here are the IPC. Jurisdictions on the UPC use different fixture-unit values for several fixtures, and the local inspector is the one who decides. Use this to size a plan and to check a quote, not to argue with an inspection.

Open the full page for this calculation →