Venting
Why traps siphon, and what the vent is doing about it.
What size vent for a 2″ drain 50 feet away?
2″ drain, 50 ft of vent
1½″
half the drain would be 1¼″, but 50 ft of developed length pushes it up 1 size
| Vent size | 1½″ |
|---|---|
| Minimum by the half-rulehalf of a 2″ drain, never below 1¼″ | 1¼″ |
| Developed lengthmeasured along the pipe — elbows, offsets and the vertical, not the straight line to the roof | 50ft |
| Length thresholdpast this, go up a size | 40ft |
| DFU a 2″ branch carries | 6DFU |
Notes
- **Two rules, and people only remember the first.** A vent is never smaller than half the drain it serves and never below 1¼″ — that gives 1¼″ here. The second rule is developed length: friction grows with the run, so a long vent has to be larger. At 50 ft that pushes this one to **1½″**.
- **Developed length is measured along the pipe.** Every elbow, every offset and the whole vertical rise count. It is not the distance from the fixture to the roof measured on a drawing — running 60 ft of 1½″ because the roof looks close is exactly how a trap at the far end gets siphoned dry.
- **What the vent actually does is protect the trap seal.** Water falling down a stack drags air with it. Without a path for replacement air, that suction pulls the water out of the nearest trap, and then sewer gas has an open door into the room. A vent that is undersized does not fail loudly — it fails as a smell nobody can place.
- **A dry trap smells the same as a broken one.** Floor drains and guest bathrooms that go months without use lose their seal to evaporation, not to venting. Before re-plumbing anything, pour a bucket of water down and wait a day.
- Figures here follow the IPC. UPC jurisdictions differ on several points — wet venting and island fixtures especially — and the local inspector decides. Use this to size a plan and to read a quote, not to argue at inspection.
Plumbing vent size
40 calculations · browse all
- What size vent for a 1.5″ drain 10 feet away?
- What size vent for a 1.5″ drain 20 feet away?
- What size vent for a 1.5″ drain 30 feet away?
- What size vent for a 1.5″ drain 40 feet away?
- What size vent for a 1.5″ drain 50 feet away?
- What size vent for a 1.5″ drain 60 feet away?
- What size vent for a 1.5″ drain 80 feet away?
- What size vent for a 1.5″ drain 100 feet away?
- What size vent for a 1.5″ drain 120 feet away?
- What size vent for a 1.5″ drain 150 feet away?
- What size vent for a 2″ drain 10 feet away?
- What size vent for a 2″ drain 20 feet away?
- What size vent for a 2″ drain 30 feet away?
- What size vent for a 2″ drain 40 feet away?
- What size vent for a 2″ drain 50 feet away?
- What size vent for a 2″ drain 60 feet away?
- What size vent for a 2″ drain 80 feet away?
- What size vent for a 2″ drain 100 feet away?
- What size vent for a 2″ drain 120 feet away?
- What size vent for a 2″ drain 150 feet away?
- What size vent for a 3″ drain 10 feet away?
- What size vent for a 3″ drain 20 feet away?
- What size vent for a 3″ drain 30 feet away?
- What size vent for a 3″ drain 40 feet away?
- What size vent for a 3″ drain 50 feet away?
- What size vent for a 3″ drain 60 feet away?
- What size vent for a 3″ drain 80 feet away?
- What size vent for a 3″ drain 100 feet away?
- What size vent for a 3″ drain 120 feet away?
- What size vent for a 3″ drain 150 feet away?
- What size vent for a 4″ drain 10 feet away?
- What size vent for a 4″ drain 20 feet away?
- What size vent for a 4″ drain 30 feet away?
- What size vent for a 4″ drain 40 feet away?
- What size vent for a 4″ drain 50 feet away?
- What size vent for a 4″ drain 60 feet away?
- What size vent for a 4″ drain 80 feet away?
- What size vent for a 4″ drain 100 feet away?
- What size vent for a 4″ drain 120 feet away?
- What size vent for a 4″ drain 150 feet away?